6.01 Troubleshooting Procedures - continued
Free Standing Ventless Hood
FSH-2 & FSH-2A-99
Troubleshooting
Problem Probable Cause Corrective Action
Fryer will not powerup:
• [HOOD POWER] light ON
• [FILTER MISSING] light ON
• [FRYER POWER] light OFF
a. Baffle filter is missing or not
properly installed
Install filter / check positioning.
b. Charcoal filter is missing or not
properly installed
Install filter / check positioning.
c. Faulty filter switches. Test & replace as needed.
Fryer will not powerup:
• [HOOD POWER] light ON
• [FILTER MISSING] light OFF
• [FRYER POWER] light OFF
• No alarm sounding
a. Fire Suppression system is not
armed.
Contact Ansul service company.
b. Ansul switch is faulty Contact Ansul service company.
Fryer will not powerup:
• [HOOD POWER] light ON
• Continuous (steady) tone alarm
sounding.
• [FRYER POWER] light OFF
a. Baffle or charcoal filter clogged
Replace the charcoal filter with a new,
clean baffle filter.
b. Hood exhaust outlet excessively
block
Clear of any obstructions.
c. Vacuum switch is out of
adjustment
Test & adjust vacuum switch.
d. Kinked or blocked vacuum line Remove vacuum line kinks or blockage.
e. Fan running slow or blades are
loaded with grease buildup.
Check voltage and inspect blower;
clean if needed
Fryer will not powerup:
• [HOOD POWERED] light ON
• [WASH] light ON
• Intermittent (beeping) tone alarm
sounding.
• [FRYER POWER] light OFF
a. Excessive grease film built up on
collector fins; too dirty
Clean the EAC cell, Section 4.04.2.
b. EAC cell is not installed Install clean EAC cell.
c. EAC driver board is faulty
Test & replace EAC power supply if
needed.
d. Poor connection at contact plate;
dirty contacts, misalignment,
faulty contacts.
Check cell position, clean contacts,
inspect contact plate & replace if
needed.
e. Ionizer wire(s) missing Replace missing wire(s)
Fryer is ON:
• [HOOD POWER] light ON
• [CHECK] light ON
• No alarm sounding, but cell is NOT
cleaning air.
a. Ionizer wire broken & touching
chassis.
Replace ionizer wire.
b. Collector fins shorted to ground
by moisture.
Dry cell, determine cause of moisture,
cool air being drawn into hood creating
condensation.