Temperature limiting can reduce energy costs
by limiting the lowest temperature that can be
set for cooling and the highest temperature that
can be set for heating. Temperature limiting is
controlled by setting the first six auxiliary
switches.
The first three are used to select cooling range
limits and the next three are used to select
heating range limits.
COOLING LIMITS
Limit Switch Temp Range
UP/On F.
None 60 to 85
1 64 to 85
1 & 2 66 to 85
2 68 to 85
2 & 3 70 to 85
1 & 2 & 3 72 to 85
1 & 3 74 to 85
3 76 to 85
HEATING LIMITS
Limit Switch Temp Range
UP/On F.
None 60 to 85
4 60 to 80
4 & 5 60 to 78
5 60 to 76
5 & 6 60 to 74
4 & 5 & 6 60 to 72
4 & 6 60 to 70
6 60 to 65
UP
DOWN
1234 56789A
B
CDE
Temperature Limiting
Auxiliary controls
The Zoneline has a diagnosis feature. When
switch D is moved to the
UP
(on) position, the
unit will go through an operations check of all
components which takes about two minutes.
This diagnostic tool is intended for use by a
qualified technician.
UP
DOWN
1234 56789A
B
CDE
Diagnosis Switch
19
Auxiliary controls