Furman ASD-120 2.0 handleiding

24 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 6 van 24
5
START
SEQUENCE
REMOTE
DLY
ADJ
DELAY A DELAY B DELAY C
PHASE
X Y Z
DELAY D DELAY E DELAY F
OFF ON
1 2 3 4 5 6 7
ASD-120 2.0
120 AMP POWER SEQUENCER
(SEE COVER PLATE)
ALWAYS ON
ALWAYS OFF
S
E
Q
INPUT 120 / 3Ø, 208 / 240 VAC
14400 WATTS – 120 AMPS MAX
20A MAX
DELAY A
20A MAX
DELAY B
20A MAX
DELAY C
20A MAX
DELAY D
20A MAX
DELAY E
20A MAX
DELAY F
FORCE OFF
DELAY OUTPUTS
REMOTE
NC A B C D E F NO
12V STAT REM GND
WARNING! ELECTRIC SHOCK HAZARD. CONNECTION OF A POWER
INPUT CABLE TO THIS DEVICE AND TO A POWER SOURCE MUST BE
DONE BY QUALIFIED PERSONNEL ONLY.
DANGER: MANIPULER SEL ON LES INSTRUCTIONS DU
FABRICANT ET CONFIER LA MAINTENANCE A UN T
ECHNICIEN QUALIFIE
DRY RELAY CONTACTS - RATING 48V / 1 AMP
Front Panel Key Switch
for Remote Security
Front Panel Start
Sequence Switch
Circuit Breakers 20A
for Delay A, B and C
Delay
Adjustment
Multi-function DIP Switch
7 Position ON/OFF
Sequence Bypass Switch
6 Position ON/SEQUENCE/OFF
Integrated Front Panel
Rack Ears
Indicator LEDs for
Delay A, B and C
Indicator LEDs for
Delay D, E and F
Indicator LEDs for
Phases X, Y and Z
Circuit Breakers 20A
for Delay D, E and F
START
SEQUENCE
REMOTE
DELAY A DELAY B DELAY C
PHASE
X Y Z
DELAY D DELAY E DELAY F
OFF ON
ASD-120 2.0
120 AMP POWER SEQUENCER
Security Cover to Protect
Program Settings
1.5” Cable Clamp
Input 120V/Phase
Six 20A duplex outlets Force Off, 2 Pin
Phoenix-type
Connector
Remote, 4 pin
Phoenix-type
connector
Delay Outputs, 8 Pin
Phoenix-type
connector
FRONT PANEL FEATURES
REAR PANEL FEATURES
PRODUCT FEATURES
• 120 Amp 120 Volt AC Sequenced Distro and Controller
• Six Independent 20 Amp Circuits @ 120Volts - 120 Amp Total Load Capacity
• Rear panel NEMA 5-20R duplex outlet and optically isolated DC relay outputs
on each of six Delay Banks.
• Front panel Status Power LED, Bypass Switch and Circuit Breaker for each
Delay Bank
• 120A power distribution block accommodates 120V/240V single phase, or
120/208-Y three phase power
• X Y Z Status LED confidence indicators for each Input Phase
• Sequence unit ON or OFF from front panel or by remote switch
• Independent three position switches to power sequence (SEQ) or Bypassed ON
or OFF each Bank
Adjustable Delay with up to 7 Minute Interval between Banks, Total maximum
Sequence Time 35 minutes
• Remote interface with an isolated 12VDC, 250mA power source for external
secondary applications.
• Signal level relay contacts (NO or NC) used to control and sequence other units.
• Front panel key switch and Anti-tamper DIP cover for added security
• Force Off emergency shutdown
• Rugged two rack space (2RU) chassis
Adjustable
Rear Mount
Rack Ears

Bekijk gratis de handleiding van Furman ASD-120 2.0, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkFurman
ModelASD-120 2.0
CategorieNiet gecategoriseerd
TaalNederlands
Grootte3501 MB