Fujitsu AJH090LNTCH handleiding

26 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 7 van 26
En-6
Fork (Forklift)
Delivery pallet
Fork (Forklift) or
Fork (Manual forklift)
<Front>
<Side>
3. 5. Installation the unit
Install the unit level. (within 3 degrees).
Install 4 or more anchor bolts at the 8 locations indicated by arrows (Fig. A).
Place the left and right anchor bolts at a distance further away than the dimensions
of A in the Table A.
(Excluding the case where anchor bolts are installed at 8 places.)
Fig. A
Hole: 12 × 17
(8 places)
Bottom view
(Unit: mm)
732
765
80
80
160160
B
A
Table.A
Model A B
AJ
072LNTCH 610 930
AJ
090LNTCH 610 930
AJ
108LNTCH 920 1240
AJ
126LNTCH 920 1240
AJ
144LNTCH 920 1240
AJ
162LNTCH 920 1240
To minimize vibration, do not install the outdoor unit directly on the ground.
Instead, install it on top of a rm platform (such as concrete block). (Fig. B)
The foundation base should be able to support the product and the foot width of
the product should be more than 46.5mm.
• Depending on the installation condition, vibration during the operation of the unit
may cause noise and vibration.
Install vibration-proo ng materials (such as rubber pads).
Consider the removal space of the connection piping when installing the founda-
tion.
• Secure the equipment rmly with anchor bolts, washers, and nuts.
Fig. B
Bolt (M10)
*Do not use a four-corner support foundation.
GOODPROHIBITED GOOD
Fig. C
200mm or
more
When installing pip-
ing from the bottom
of the outdoor units,
the required space
under the outdoor
unit 200mm.
* Install the branch
kit horizontally.
4. SYSTEM CONFIGURATION
4. 1. System con guration
CAUTION
• When connecting multiple outdoor units, set the nearest outdoor unit to the indoor
unit on the refrigerant pipe as the master unit.
• When connecting multiple outdoor units, install the outdoor unit with the largest
nominal system capacity nearest to the indoor unit on the refrigerant pipe, fol-
lowed by those with less nominal system capacities.
[Capacity: Master Slave]
Always keep to the limit on the total amount of refrigerant. Exceeding the limit
on the total amount of refrigerant when charging will lead to malfunction.
A) In case of 1 outdoor unit connected
Fig. A
O.U.
(Master)
O.U. :Outdoor unit
I.U. :Indoor unit
I.U.
I.U. I.U. I.U.
I.U.
I.U. I.U. I.U. I.U.
f
p
H2
H1
H3
a
g
q
Allowable pipe length (actual pipe length)
Between master outdoor unit and the
farthest indoor unit
165 m or less
a+f
a+p
Between the rst separation tube and the
farthest indoor unit
90 m or less f, p
(farthest indoor unit)-(closest indoor unit) 60 m or less f (p) - g (q)
Total pipe length 700 m or less Total
• Allowable height di erence
Between outdoor unit and indoor unit (When
indoor unit is installed below)
50 m or less
H1
Between outdoor unit and indoor unit (When
outdoor unit is installed below)
40 m or less
Between indoor units 15 m or less H2, H3
Total refrigerant amount : 31.5 kg or less
B) In case of 2 outdoor units connected
Fig. B
O.U.-2
(Slave)
O.U.-1
(Master)
f
e
a
g
q
H4
p
H1
H2
H3
b
O.U. :Outdoor unit
I.U. :Indoor unit
I.U.
I.U.
I.U.
I.U.
I.U.
I.U.
I.U.
I.U. I.U.
Allowable pipe length (actual pipe length)
Between master outdoor unit and the
farthest indoor unit
165 m or less
a+e+f
a+e+p
Between the rst separation tube and the
farthest indoor unit
90 m or less f, p
(farthest indoor unit)-(closest indoor unit) 60 m or less f (p) - g (q)
Total pipe length 1000 m or less Total
Between outdoor unit and outdoor unit
branch kit
3 m or less a, b
9378945623-02_IM_EN.indd 69378945623-02_IM_EN.indd 6 2022/10/28 8:43:17 AM2022/10/28 8:43:17 AM