Fujitsu AJG072JATAH handleiding

24 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 15 van 24
En-15
6.6.3 Connecting cables to the terminals
WARNING
Use ring terminals and tighten the terminal screws to the specified torques, otherwise,
abnormal overheating may be produced and possibly cause heavy damage inside the
unit.
Be sure fill the holes of power supply cable, transmission cable and electrical wires with
insulation (accessory) or putty (locally purchased).
Ifsmallanimalssuchasinsectsentertheelectricalcomponentbox,ashortcircuitmay
be caused.
How to connect wiring to the terminal
Caution when wiring cable
(1) Use ring terminals with insulating sleeves as shown in the figure to connect to the
terminal block.
(2) Securely clamp the ring terminals to the cables using an appropriate tool so that
the cables do not come loose.
(3) Use the specified cables, connect them securely, and fasten them so that there is
no stress placed on the terminals.
(4) Use an appropriate screwdriver to tighten the terminal screws. Do not use a screw-
driver that is too small, otherwise, the screw heads may be damaged and prevent
the screws from being properly tightened.
(5) Do not tighten the terminal screws too much, otherwise, the screws may break.
(6) See the table below for the terminal screw tightening torques.
Tightening torque
M3 screw 0.5 to 0.6 N·m (5 to 6 kgf·cm)
M5 screw 2.0 to 3.0 N·m (20 to 30 kgf·cm)
Strip 10 mm
Cable
Screw with
special washer
Ring terminal
Terminal block
Ring terminal
Sleeve
Screw with
special washer
Ring terminal
Cable
6.6.4 Connecting the power supply cable
Ring terminal: M5
Ground cable
70 to 80 mm
110 to 120 mm
* Use a ring terminal to connect the electric cables to the power supply terminal board.
6.6.5 Connecting the transmission cable
Shielding the transmission cable
Connect both ends of the shielded
wire of the transmission cable to
the earth (ground) terminal of the
equipment or to the earth (ground)
screw near the terminal.
Be sure to use one side of a
twisted-pair cable when using
transmission cable with 2 sets of
twisted-pair cables.
Wind with insulation tape to prevent short circuit
Use one side
of the twisted
pair cable
Connect both ends of shielded
wire to earth (Ground).
RB
IN
Cable clip
Cable tie
(accessory)
40 mm or more
8 to 10 mm
6.7. External input and external output
6.7.1 Terminal position
CN131
EXT. IN. 1
CN133
EXT. IN. 3
CN134
EXT. IN. 4
CN135
PULSE IN
CN136
EXT. OUT. 1
CN137
EXT. OUT. 2
(1)
(6)
(5)
(2) (3) (4)
Main PC board
Terminal
Application
Number Name Color
(1) CN131 EXT. IN. 1 Brown Forexternalinput
(2) CN133 EXT. IN. 3 White
(3) CN134 EXT. IN. 4 Purple
(4) CN135 PULSE IN Orange
(5) CN136 EXT. OUT. 1 Black Forexternaloutput
(6) CN137 EXT. OUT. 2 Blue
6.7.2 Optional cable routing
Cable guide
The optional parts cables are
bound with the cable ties (acces-
sory) and cable clips together with
the transmission cable.
Power supply cable routing
Transmission cable routing
9378945746-01_IM_En_240313.indd 159378945746-01_IM_En_240313.indd 15 2024/03/14 8:55:122024/03/14 8:55:12