En-13
6.5. Transmission line
CAUTION
Caution when wiring cable:
Whenstrippingoffthecoatingofleadwire,alwaysusetheexclusivetoolsuchasa
wirestripper.Ifthereisnoexclusivetoolavailablenecessarily,carefullystripthecoat-
ing by a cutter etc. so that the conductive wire is not damaged.
If it is damaged, it may lead to an open circuit and a communication error.
Pay attention to the following points while attaching wires on the terminal board.
• Do not attach 2 wires on one side.
• Do not twist wires.
• Do not cross the wires.
• Do not shorted at edge at root.
GOOD PROHIBITED
1 wire 2 pcs at one side Wires twisted
2 wires Shorted at edge Shorted at root
6.5.1 Transmission wiring specications
Follow the specifications below for the transmission cable.
Use Size Cable type Remarks
Transmission cable 0.33mm²
22AWG LEVEL 4 (NEMA)
nonpolar 2 core, twisted pair
solid core diameter 0.65 mm
LONWORKS ®
compatible cable
Twisted pair with shielded type.
Use the shielded wire specified and always ground it both ends.
6.5.2 Wiring rules
(1) Total length of transmission cable
Totaltransmissionlinelength:Max.3,600m
EF+EG+GH+HJ+HK+KL<3,600m(Fig.2)
In the following cases , Signal Amplifier is required.
Whenthetotallengthofthetransmissionlineexceeded500m.
1)AB+BC+BD>500m(Fig.1)
2) When the total number of units* is over 64.
3)Transmissionlinelengthbetweeneachunit*≥400m
(2) Length of transmission cable between 1 network segment (NS)
EF+EG+GH+HJ+HK≤500m(Fig.2)
KL≤400m(Fig.2)
(3) Length of transmission cable between outdoor units in a refrigerant system
MN≤18m
NP≤18m
Fig. 1
A
B
C
D
Transmission line
Outdoor unit
Indoor unit
System
controller
Touch panel
controller
Terminal
resistor
WhenAB+BC+BD>500m:
Signal Amplifier is required.
Fig. 2
NS 1
NS 2
F
H
L
G
K
J
E
P
M
N
Outdoor unit
Indoor unit
Signal Amplifier
System
controller
Touch panel
controller
Transmission line
Terminal resistor
Terminal resistor
Length of the grommet edging Mounting the grommet edging
Grommet edging
(accessories)
Knockout
Knockout diam-
eter (mm)
Dimension L
(mm)
Ø 50 147
Ø 43.7 130
Ø 34.5 100
Ø 22.2 60
6.4. Selecting power supply cable and breaker
CAUTION
Obtain the distribution network operator's agreement about the power capacity of the
power supply system, specification of the cable and the harmonic current, and etc.
when you connect the outdoor unit with the power supply.
Regulation of wire size and circuit breaker differs from each locality, please refer in ac-
cordance with local rules.
Refer to the table for the wiring and breaker specifications of each installation condition.
(1) Selecting power supply cable and breaker when connecting 1 outdoor unit
Model
Breaker (Time delay fuse
or circuit capacity)
Outdoor unit power supply cable
Recommended cable size
(mm²)
Limited wir-
ing length
(m)
Fuse capac-
ity (A)
Leakage
current
Power cable
Earth
(ground)
cable
AJG072JATAH
20
100 mA
0.1 sec or
less
6 6 62
AJG090JATAH
25 6 6 62
AJG108JATAH
25 6 6 62
AJG126JATAH
30 10 10 64
AJG144JATAH
35 10 10 64
AJG162JATAH
35 10 10 64
AJG180JATAH
40 10 10 64
These values are recommended data.
• Specification: Use conformed cord with Type 60245 IEC66
Max.wirelength:Setalengthsothatthevoltagedropislessthan2%.Increasethewire
diameter when the wire length is long.
In case of connected outdoor unit
3N~ 380-415V 50Hz
3N~ 400V 60H
z
230V ~ 50Hz
GOOD
Transmission cable
Remote controller cable
Breaker
Breaker
Outdoor unit
Power supply cable
Indoor unit
Power supply cable
(2) Selecting main breaker and main power supply cable when connecting multiple
outdoor units
3N~ 380-415V 50Hz
3N~ 400V 60Hz
GOOD
Sub breaker
Outdoor unit power supply cable
Main breaker
Mainbreaker:Mainbreaker≥TotalSubbreaker(Refertothetableinitem(1)forthe
sub breaker capacity)
Example of prohibited breaker wiring
Breaker:
Connecting multiple outdoor units
to one breaker is prohibited.
Outdoor unit power supply cable:
Crossover wiring between outdoor units is prohibited.
3N~ 380-415V 50Hz
3N~ 400V 60Hz
9378945746-01_IM_En_240313.indd 139378945746-01_IM_En_240313.indd 13 2024/03/14 8:55:102024/03/14 8:55:10