COMPONENT TESTING
Check Outdoor Fan Motor
1.
Remove power from unit.
2. Remove Front Panel. (Refer to Chassis Removal)(Figure 701)
3. Open electrical box (Refer to figures 702 thru 705).
4. Apply power to unit.
5. Check voltage at Outdoor motor control terminals.
a. White (L2) to Black (Condpump) VAC (Should read Supply line
Voltage).
b. If No voltage is present replace PCB (refer to figure 706).
6. Check outdoor fan capacitor (CP2)
If capacitor checks good;
7. Check fan motor windings resistance;
a. Remove power from unit.
b. Disconnect wires from main pcb and capacitor
c. Check resistance
Resistance values across legs should be similar.
Replace motor if windings check bad.
WARNING
RISK OF ELECTRIC SHOCK
Unplug and/or disconnect all electrical power
to the unit before performing inspections,
maintenances or service.
Failure to do so could result in electric shock,
serious injury or death.
cond/pump
terminal
L2
Figure 513