TROUBLESHOOTING
Malfunction of Temperature Sensor
E2/E3/E4/E5
1. Remove Power from Unit.
2. Remove front Panel.
3. Open electrical Control Box.
4. Using a multi meter ohm across applicable pins for the sensor you are checking.
5. Refer to thermistor charts in Appendix for resistance and temperature deviation.
E2 Error 5k Room Temp. Sensor (T1).
E3 Error 5k Evaporator Coil Temp Sensor (T2).
E5 Error 5k Condenser coil temp sensor (T3).
E7 Error 5k Outdoor ambient temp sensor (T4).
6. Replace sensor if open or if resistance values deviate by more than 10% of the listed values.
T4 Ambient temperature sensor
T1 Indoor Temp Sensor
T2 Evaporator coil sensor
T3 Condenser coil temp sensor