Friedrich ZoneAire Premier ZHV16DA handleiding

96 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 9 van 96
9
awarded by the authoritative organization and the qualification for dealing with the refrigeration
system recognized by this industry. If it needs other technicians to maintain and repair the
appliance, they should be supervised by the person who bears the qualification for using the
flammable refrigerant.
2 REPAIRS TO SEALED COMPONENTS
Sealed electrical components shall be replaced.
3 REPAIRS TO INTRINSICALLY SAFE COMPONENTS
Intrinsically safe components must be replaced.
4 CABLING
Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp
edges or any other adverse environmental effects. The check shall also consider the effects of
aging or continual vibration from sources such as compressors or fans.
5 DETECTIONS OF FLAMMABLE REFRIGERANTS
Under no circumstances shall potentially sources of ignition be used in the searching for or
detection of refrigerant leaks. A halide torch (or any other detector using a naked flame)
shall not be used.
6 LEAK DETECTION METHODS
The following leak detection methods are deemed acceptable for systems containing
flammable refrigerants. Electronic leak detectors shall be used to detect flammable refrigerants,
but the sensitivity may not be adequate or may need recalibration. (Detection equipment shall be
calibrated in a refrigerant-free area.) Ensure that the detector is not a potential source of
ignition and is suitable for the refrigerant used. Leak detection equipment shall be set at a