DIAG
CODE
PROBLEM
CONDITIONS POSSIBLE CAUSES CORRECTIVE ACTION
18 (CONT)
Inverter
immediate
fault 1
Continued
7802
DC Bus Over
Voltage
The DC voltage on the electrolytic
capacitor exceeds the set limit value
1. After power is on.
2. The DC voltage on the electrolytic
capacitor exceeds the set limit
value.
3. If the above conditions are met. it
will report the fault to Display Board
for 3 minutes continuously.
1. The voltage of power supply is
too high.
1. Power supply voltage > 230 VAC
for 115 V power. 300 VAC for 230V
power.
1. Check wiring and connections from PCB to
compressor.
2. Disconnect the compressor before power up
the unit and check for fault. If fault is removed
replace compressor.
3. Check the voltage of power supply.
4. Check the radiator ventilation is normal.
5. Check whether the IPM is in good contact with
the radiator.
6. Check refrigeration system for abnormalities.
7. Replace Inverter PCB.
8. Replace Compressor.
7803
DC Bus Under
Voltage
The DC voltage on the electrolytic
capacitor is lower than the set limit
value.
1. After power is on.
2. The DC voltage on the electrolytic
capacitor exceeds the set limit value
3. If the above conditions are met. it
will report the fault to Display Board
for 3 minutes continuously.
1. The voltage of power supply is
too low.
1. Power supply voltage < 78 VAC
for 115V power. 120 VAC for 230V
power.
2. PCB is faulty.
7811
Compressor
Power Module
Over Temperature
IPM module temperature exceeds
the set limit value.
1. Detect the fault when the
compressor is running;
2. IPM module temperature exceeds
the set limit value.
3. If the above conditions are
met. the unit will shut down for 3
minutes, error will be reported.
1. The radiator ventilation is
abnormal
2. Poor contact between IPM and
radiator or screws are loose.
3. PCB is faulty.
7815
Pre-Charge Relay
Open
This fault occurs when the voltage
between DC + and DC -is lower than
100V when power on for the first
time.
1. Detection at initial power on of
ODU;
2. the voltage between DC + and DC
-is lower than 100V.
3. If the above conditions happed,
error will be reported, and unit will
be shut down.
1. The voltage of power supply is
too low. Power supply voltage
< 70 VAC;
2. PCB is faulty.
7807
PFC Desaturation
1. Detect the fault when the PFC is
on.
2. The AC Peak current is detected
to exceed the set limit value.
3. If the above conditions are
met. the unit will shut down for 3
minutes, error will be reported.
1. The voltage of power supply is
too low or too high.
2. Wiring loose or disconnected.
3. Inverter PCB Faulty.
TROUBLESHOOTING
Diagnostic Codes-Inverter