Friedrich Hazardgard SH20M30B handleiding

90 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 24 van 90
24
Chassis Wiring and Preparation (ATEX & IECEx Models)
Figure 34
EXTERNAL GROUND
-See Note-
NOTE: This air conditioner shall be installed in accordance with national wiring regulations of the country where installed.
Electrical connections to equipment must only be carried out by qualied personnel per NEC/CEC 501.10 (B) EN/IEC 60079-14.
Repairs affecting hazard location protection must be carried out by a qualied electrician in accordance with NEC/CEC 501.10
(B) EN/IEC 60079-19.
STEP 4 Complete junction box wiring, cover and tighten cover screws (Figure 34-6) to prevent ingress from dust and moisture.
NOTE: Per EN/IEC 60079-0, external grounding or earthing may be necessary.
If required, use provided external ground clamp which can accept two cables of up to 6mm (Figure34-7).
INSTALLATION
ELECTRICAL JUNCTION
BOX
WITH EMI FILTER
Figure 35

Bekijk gratis de handleiding van Friedrich Hazardgard SH20M30B, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkFriedrich
ModelHazardgard SH20M30B
CategorieAirco
TaalNederlands
Grootte21697 MB