7.2 TABLE OF ALARMS REPORTED ON THE CH193VMC DISPLAY
Below is the table of unit operating anomalies reported on the remote display.
CODE DESCRIPTION CAUSE SOLUTION
VMC: AIR Return Probe Alarm Broken probe and failed
reading
Check the connection of the
probe or replace it
VMC:
MOTOR
Fan alarm Fan connector or no feedback
signal
Check the connection of the
board to the fan
VMC: H2 H2 Exhaust Probe alarm Broken probe and failed
reading
Check the connection of the
probe or replace it
VMC: H4 H4 outdoor air probe alarm Broken probe and failed
reading
Check the connection of the
probe or replace it
VMC: COM Communication alarm Check the green led on the
board;
Check the status of the
indicator led on the board
Dirty filter alarm
VMC: FILTER Dirty filter alarm Elapsed hours of operation for
dirty filter (default = 0)
Check the state of the filter
and enter the CH193VMC
menu to reset the warning;
VMC: UVC UVC led alarm Elapsed hours of operation for
UVC led
Check the state of the UVC
led lamp, replace it and
reset the warning of the
remote panel