Extech 382357 handleiding
Handleiding
Je bekijkt pagina 4 van 13

382357‐EU‐ENV2.42/13
4
Operation
Note:Ensurethatthejawsarefullyclosedbeforetesting.
Note:DONOTclampontoanyconductororopentheclampjawsduringthestart‐upself‐
calibration(self‐calisidentifiedbytheLCDcountingdownfromCAL7toCAL1).
GroundResistanceMeasurements
1. Opentheclampjawsandcheckthatallsurfacesare
cleanandfreeofdust,dirt,oranyforeign
substances.Cleanifnecessary.
2. Forcefullysnaptheclampjawsopenandclosed
severaltimes.
3. Turnthemeteronbymovingtherotaryswitchto
theohms
position.DONOTinterruptthestartup
procedurebyopeningtheclampjawsorclamping
aroundaconductor.Duringself‐calibration,the
meterwilldisplayCAL5,CAL4,CAL3,CAL2and
CAL1.
4. Oncethestart‐upcalibrationprocedureiscompleted,themeterwillsoundabeep.Clamp
ontoanelectrodeorgroundrodandreadthevalueofground resistanceonthedisplay.
Ground/LeakageCurrentMeasurement
1. Turnthemeteronbymovingtherotaryswitchtothe
mAorAposition.
2. Clampontotheelectrodeorconductor
3. Readthevalueofleakagecurrentdisplayedonthe
LCD.
HOLD
PresstheHOLDbuttontofreezethereadinginthedisplay.Hwillappearinthedisplay.Press
HOLDagaintoexitthefunction.