41 Automatic settings
Control System KNX WS1000 Style • Version: 28.05.2018 • Technical changes and errors excepted.
Confirm your setting with the OK button.
Press the button to set the supply air temperature block (heat protection).
Enable:
If the window should be closed when the air supply temperature is higher than
the room temperature, select Yes.
The supply air temperature-block becomes active as soon as the incoming air temper-
ature lies above the room temperature. The block is however only deactivated again
when the incoming air temperature sinks below the room temperature by more than
3.0°C (hysteresis).
Disable:
If the window should also then be/remain open when the supply air tempera-
ture is higher than the room temperature, select No (default setting).
Confirm your setting with the OK button.
Press the button to set the movement position for a sliding window in automatic mode.
The window can also be fully opened by hand.
With the arrow keys, specify the movement position in % (0% = closed, 100% = fully
open). Default setting: 75%.
Confirm your setting with the OK button.
Press the button to set the number of movement steps for a step window in automatic
mode. With step windows the control unit checks every 3 minutes whether the set
room temperature or air humidity has been exceeded and then moves up another step
if necessary.
Specify the desired number of steps with the arrow keys. Default setting: 5.
Confirm your setting with the OK button.
Press the button to set the times for night-time re-cooling. The button is only activated
once the general settings for night-time re-cooling have been configured.
System > Automatic Settings > General Settings > Night-time Cooling
3.3. Set night-time re-cooling
Press Select to select the time during which the night-time re-cooling will operate. Ac-
tivate one or more periods on the list.
Supply-Air Temp.
Movem. Position
Only for sliding windows.
Number of steps
Only for step windows.
Night-time cooling