16 Transfer protocol
Sensor KNX VOC/TH-UP Touch • Version: 30.11.2021 • Technical changes and errors excepted.
60 Internal measured value for humi-
dity
Output R-CT [9.7] DPT_Value_Hu-
midity
2 Bytes
61 Total measured value for humidity Output R-CT [9.7] DPT_Value_Hu-
midity
2 Bytes
62 Request min./max. humidity mea-
sured value
Input -WC- [1.17] DPT_Trigger 1 Bit
63 Minimum measured value for
humidity
Output R-CT [9.7] DPT_Value_Hu-
midity
2 Bytes
64 Maximum measured value for
humidity
Output R-CT [9.7] DPT_Value_Hu-
midity
2 Bytes
65 Reset min./max. measured value
for air humidity
Input -WC- [1.17] DPT_Trigger 1 Bit
66 Humidity thresholdV 1: Absolute
value
Input /
Output
RWC
T
[9.7] DPT_Value_Hu-
midity
2 Bytes
67 Humidity thresholdV 1: (1:+ | 0:-) Input -WC- [1.2] DPT_Bool 1 Bit
68 Humidity thresholdV 1: Switching
delay from 0 to 1
Input -WC- [7.5] DPT_TimePeri-
odSec
2 Bytes
69 Humidity thresholdV 1: Switching
delay from 1 to 0
Input -WC- [7.5] DPT_TimePeri-
odSec
2 Bytes
70 Humidity thresholdV 1: Switching
output
Output R-CT [1.1] DPT_Switch 1 Bit
71 Humidity thresholdV 1: Switching
output block
Input -WC- [1.2] DPT_Bool 1 Bit
72 Humidity thresholdV 2: Absolute
value
Input /
Output
RWC
T
[9.7] DPT_Value_Hu-
midity
2 Bytes
73 Humidity thresholdV 2: (1:+ | 0:- ) Input -WC- [1.2] DPT_Bool 1 Bit
74 Humidity thresholdV 2: Switching
delay from 0 to 1
Input -WC- [7.5] DPT_TimePeri-
odSec
2 Bytes
75 Humidity thresholdV 2: Switching
delay from 1 to 0
Input -WC- [7.5] DPT_TimePeri-
odSec
2 Bytes
76 Humidity thresholdV 2: Switching
output
Output R-CT [1.1] DPT_Switch 1 Bit
77 Humidity thresholdV 2: Switching
output block
Input -WC- [1.2] DPT_Bool 1 Bit
78 Humidity control: Blocking object Input -WC- [1.2] DPT_Bool 1 Bit
79 Humidity control: Target value Input /
Output
RWC
T
[9.7] DPT_Value_Hu-
midity
2 Bytes
80 Humidity control: Target value (1:+ |
0:-)
Input -WC- [1.2] DPT_Bool 1 Bit
81 Humidity control: Act. variable
dehumidification
Output R-CT [5.1] DPT_Scaling 1 Byte
82 Humidity control: Act. variable
dehumid. 2nd stage
Output R-CT [5.1] DPT_Scaling 1 Byte
No Text Function Flags DPT type Size