38 Initial start-up
Room Controller KNX Touch One Style • Status: 30.07.2020 • Errors excepted. Subject to technical changes.
3.1. First commissioning
Installation, inspection, commissioning and troubleshooting of
the device must only be carried out by a competent electrician.
3.1.1. Boot the control system
Bringing a device from a cold room into a warm room can cause
a build-up of condensation. Before commissioning, ensure that
there is no humidity in the device (leave to dry if necessary).
After installation, wiring up the equipment and verifying all connections, switch on the
auxiliary supply.
Once the Start-up test sequence has been successfully completed, the Control system
in the Start menu is in its start position.
3.1.2. Check the function of the sensors
The current values for the room interior sensors for room temperature and air humidity
are shown on the display.
If the measured values of the integrated sensor are affected by external influences
(sources of interference like direct sunlight), they can be corrected manually. It is alos
possible to set an external proportion.
Technical Data, page 6
TH sensor, page 73
3.1.3. Addressing the unit
The physical address is assigned using the display screen menu Settings > Phys. Ad-
dress. Press the buttons:
The Physical Address menu displays the current address and the status of the pro-
gramming LED (the address is 15.15.255 on delivery).
Phys. Adrdess
Press the Programming button, in order to address the device to the bus.