41 Parameter setting
Sensor KNX TH-UP Touch • Version: 05.09.2022 • Technical changes and errors excepted.
6.11. Comfort field
The Sensor KNX TH-UP Touch can send a message to the bus if the limits of the
comfort field are exceeded. In this way, it is for example possible to monitor compli-
ance with DIN 1946 (standard values) or even to define your own comfort field.
Define the comfort field by specifying the minimum and maximum values for temper-
ature and humidity. The specified standard values comply with DIN 1946
Temperature hysteresis: 1°C
Relative humidity hysteresis: 2% RH
Absolute humidity hysteresis: 2 g/kg
6.12. Variable comparator
The two integrated control variable comparators can output maximum, minimum and
median values.
Use absolute humidity No • Yes
Sending pattern never
periodically
on change
on change and periodically
At and above change of
(if sent on change)
0,1 g • 0,2 g • 0,5 g • 1,0 g • 2,0 g • 5,0 g
Send cycle
(if sent periodically)
5 s • 10 s • 30 s… • 2 h
Use comfort field No • Yes
Sending pattern • never
• periodically
• on change
• on change and periodically
Send cycle (if sent periodically) 5 s • 10 s • 30 s… • 2 h
Maximum temperature in °C
(Standard 26°C)
25 ... 40; 26
Minimum temperature in °C
(Standard 20°C)
10 ... 21; 20
Maximum relative humidity in %
(Standard 65%)
52 ... 90; 65
Minimum relative humidity in %
(Standard 30%)
10 ... 43; 30
Maximum absolute humidity in 0.1 g/kg
(Standard 115 g/kg)
50 ... 200; 115
Use comparator 1/2 No • Yes