26 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 02.08.2022 • Technical changes and errors excepted.
Specify when the current control variables of the controller are to be sent to the bus.
Periodic sending is safer, in case a message does not reach a recipient. You may also
set up periodical monitoring by the actuator with this setting.
The status object reports the current status of the control variables (0% = OFF,
>0% = ON) and may for example be used for visualisation, or to switch off the
heating pump as soon as the heating is switched off.
Then define the type of control. Heating and/or cooling may be controlled in two lev-
els.
General set point values
You may enter separate set point values for each mode or use the comfort set point as
a basic value.
If you are using the controls for both heating and cooling, you may also select the
setting "separately with switching object". Systems used for cooling in the summer
and for heating in the winter can thus be switched from one to the other.
If you are using the basic value, only the deviation from the comfort set point value is
listed for the other modes (e. g., 2°C less for standby mode).
Send control variable • on change
• on change and periodically
from change (in % absolute) 1...10; 2
Cycle
(if sent periodically)
5 s • ... • 5 min • … • 2 h
Send status objects • on change
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically
Cycle
(if sent periodically)
5 s • ... • 5 min • … • 2 h
Type of control • Single level heating
• Dual-level heating
• Single-level cooling
• Single-level heating + single-level cooling
• Dual-level heating + single-level cooling
• Dual-level heating + dual-level cooling
Preserve modified set points after mode
change
No • Yes
Setting the nominal values • separate with switching object
• separate without switching object
• with comfort set point as a basis