29 Description
Display Corlo Touch KNX • Status: 30.08.2021 • Technical changes and errors reserved.
625 660 695 730 765 Temp. controller:
Set point, standby
cooling(1:+ | 0:-)
Input 1.002 C W
626 661 696 731 766 Temp. controller:
Set point, eco
heating
Input /
Output
9.001 C R W
T
627 662 697 732 767 Temp. controller:
Set point, eco
heating (1:+ | 0:-)
Input 1.002 C W
628 663 698 733 768 Temp. controller:
Set point, Eco
cooling
Input /
Output
9.001 C R W
T
629 664 699 734 769 Temp. controller:
Set point, eco
cooling (1:+ | 0:-)
Input 1.002 C W
630 665 700 735 770 Temp. controller:
Control variable,
heating (level 1)
Output 5.001 C R T
631 666 701 736 771 Temp. controller:
Control variable,
Heating (level 2)
Output 5.001 C R T
632 667 702 737 772 Temp. controller:
Control variable,
cooling level 1
Output 5.001 C R T
633 668 703 738 773 Temp. controller:
Control variable,
Cooling (level 2)
Output 5.001 C R T
634 669 704 739 774 Temp. controller:
Status – Heating 1
(1=ON | 0=OFF)
Output 1.002 C R T
635 670 705 740 775 Temp. controller:
Status – Heating 2
(1=ON | 0=OFF)
Output 1.002 C R T
636 671 706 741 776 Temp. controller:
Status – Cooling 1
(1=ON | 0=OFF)
Output 1.002 C R T
637 672 707 742 777 Temp. controller:
Status – Cooling 2
(1=ON | 0=OFF)
Output 1.002 C R T
No.
Auto
1
No.
Auto
2
No.
Auto
3
No.
Auto
4
No.
Auto
5
Name Functio
n
DPT Flags