105 Humidity parameter settings
Room Controller Cala Touch KNX • Version: 13.07.2022 • Technical changes and errors excepted.
8.4. Dewpoint measurement
The Room Controller Cala Touch KNX calculates the dewpoint temperature and
can output the value to the bus.
Activate the monitoring of the coolant temperature if required. The menus for setting
the monitoring are displayed.
8.4.1. Cooling medium temp. monitoring
A threshold value can be set for the temperature of the coolant, which is based on the
current dewpoint temperature (offset/deviation). The switching output of the coolant
temperature monitoring system can provide a warning prior to any build-up of conden-
sation in the system, and/or activate appropriate countermeasures.
Threshold value
Threshold value = dewpoint temperature + offset
Set, in which cases offset received via object is to be retained. Please note that the set-
ting "After power supply restoration and programming" should not be used for the in-
itial start-up, as the factory settings are always used until the first communication (set-
ting via objects is ignored).
During initial commissioning, an offset must be defined which is valid until the first
communication of a new offset. For units which have already been taken into service,
the last communicated offset can be used.
Sending pattern • never
• periodically
• on change
• on change and periodically
At and above change of
(if sent on change)
0.1°C • 0.2°C • 0.5°C • 1.0°C • 2.0°C • 5.0°C
Send cycle
(if sent periodically)
5 s • 10 s • 30 s • 1 min • … • 2 h
Use monitoring of the coolant temperature No • Yes
Maintain the
offset received via communication object • never
• after power supply restoration
• after power supply restoration and
programming
.