8.4.7 Conguration 7: All EV chargers in daisy-chain to router
All EV chargers connected to the internet via Ethernet router in daisy-chain topology using RJ45 cable as part of the existing
network infrastructure.
This is the configuration recommended if you are using Eaton Building Energy Management Software.
The maximum number of connected EV chargers in this configuration is 50. In this configuration there is not a subnetwork
managed by the Master. All the EV chargers are part of the existing network infrastructure and range of IP. When creating a
daisy-chain network using RJ45 cable, it is important to consider the locations of the Ethernet ports on the EV charger:
•
ETH0 (left port) of the Master should be connected to the ETH1 (right port) of Node 1.
•
ETH0 (left port) of Node 1 should be connected to the ETH1 (right port) of Node 2.
•
ETH0 (left port) of Node (n-1) should be connected to the ETH1 (right port) of Node (n).
Figure 74. Network diagram: All EV chargers connected via Ethernet router in daisy-chain in a bridge configuration.
If an EV charger acting as a Node fails in this network configuration, all Nodes that are connected to the right of the
chain from the point of failure will be unable to communicate with the Master and will be unavailable.
This configuration only works if the ethernet router can provide a DHCP and DNS servers.
Recommended configuration to work with Eaton’s BEMS or any other configuration that requires to have all the
EV chargers in the same network as the existing network infrastructure.
8.4.7.1 Network connection settings
Configuring the Master and Nodes includes setting up ETH0 and ETH1 port parameters as a bridge. A qualified
person performing the installation should have a good understanding of IP network installation and commissioning.
To configure the Master and Node, select the advanced configuration first (refer to Section 8.4.3.2 for details).
Set up all the EV Chargers in a daisy-chain network topology, refer to Section 8.4.3.2.
95GREEN MOTION BUILDING INSTALLATION MANUAL MN191028EN April 2024 www.eaton.com