Table 9. Eaton recommendations for protective devices for the Green Motion Building EV charger
Type
Reference
40 A breaker for the three-phase 32 A charging current PLSM-C40/3N-MW
20 A breaker for the three-phase 16 A charging current PLSM-C20/3N-MW
RCD type A for the three-phase 32 A charging current PFIM-40/4/003-A-MW
RCD type A for the three-phase 16 A charging current PFIM-25/4/003-A-MW
20 A RCBO (MCB+RCD Type A) for the three-phase 16 A charging current MRB4-20/3N/C/003-A
20 A breaker for single-phase 16 A charging current EMCH120
40 A breaker for single-phase 32 A charging current EMCH140
6.3 Electrical connection and terminals
Step 1. Open the housing of the Green Motion Building EV charger. Refer to subsection 5.2 of this manual for detailed
instructions.
Step 2. Insert the power supply cable through the cable gland on the bottom of the EV charger. Remove the cable glands, if
necessary.
Step 3. Connect the wires of the AC grid to the top or the bottom of the power supply terminals.
It is prohibited to connect the unit terminals to a circuit with a 3-phase IT grid configuration.
Before starting the connection operations, ensure that the external AC-line main switch is disconnected, and circuit
breakers are open.
Eaton recommends the use of the following equipment as protective devices.
In case of three phases, connect the phase (L1, L2, L3), neutral (N) and earth (PE) wires of the AC (distribution) grid to
the power supply terminal block in the Green Motion Building EV charger,
respecting the correct assignment:
•
Phase (L1) L1 terminal
•
Phase (L2) L2 terminal
•
Phase (L3) L3 terminal
•
Neutral (N) N terminal
•
Earth (PE) PE terminal
Be careful not to confuse the phases with the neutral. The device can malfunction in case of incorrect wiring.
The electronic platform does not need to be dismantled to perform wiring. Doing so will void the product warranty.
The installer should refer to local installation regulations to select the correct protection device.
In case of single phase, connect the phase (L1 OR L2 OR L3), neutral (N) and earth (PE) wires of the AC (distribution)
grid to the power supply terminal block, respecting the correct assignment:
•
Phase (L1) OR Phase (L2) OR Phase (L3) L1 terminal
•
Neutral (N) N terminal
•
Earth (PE) PE terminal
30
GREEN MOTION BUILDING INSTALLATION MANUAL MN191028EN April 2024 www.eaton.com