1.   Transport of equipment containing flammable refrigerants - see transport 
regulations
2.  Marking of equipment using signs - see local regulations
3.  Disposal of equipment using flammable refrigerants - see national regulations.
4.   Storage of equipment/appliances - The storage of equipment should be in 
accordance with the manufacturer’s instructions.
5.   Storage of packed (unsold) equipment - storage package protection should be 
constructed such that mechanical damage to the equipment inside the package 
will not cause a leak of the refrigerant charge. The maximum number of pieces of 
equipment permitted to be stored together will be determined by local regulations.
6.  Information on servicing
•  Checks to the area
   Prior to beginning work on systems containing flammable refrigerants, safety 
checks are necessary to ensure that the risk of ignition is minimised. For repair to 
the refrigerating system, the following precautions shall be complied with prior to 
conducting work on the system.
•  Work procedure
   Work shall be undertaken under a controlled procedure so as to minimise the risk of 
a flammable gas or vapour being present while the work is being performed.
•  General work area
   All maintenance sta and others working in the local area shall be instructed on the 
nature of work being carried out. Work in confined spaces shall be avoided. The 
area around the workspace shall be sectioned o. Ensure that the conditions within 
the area have been made safe by control of flammable material.
•  Checking for presence of refrigerant
    The area shall be checked with an appropriate refrigerant detector prior to 
and during work, to ensure the technician is aware of potentially flammable 
atmospheres. Ensure that the leak detection equipment being used is suitable for 
use with flammable refrigerants, i.e. non-sparking, adequately sealed or intrinsically 
safe.
•  Presence of fire extinguisher
   If any hot work is to be conducted on the refrigeration equipment or any associated 
parts, appropriate fire extinguishing equipment shall be available to hand. Have a 
dry powder or CO2 fire extinguisher adjacent to the charging area.
•  No ignition sources
   No person carrying out work in relation to a refrigeration system which involves 
exposing any pipe work that contains or has contained flammable refrigerant shall 
use any sources of ignition in such a manner that it may lead to the risk of fire or 
explosion. All possible ignition sources, including cigarette smoking, should be kept 
suciently far away from the site of installation, repairing, removing and disposal, 
during which flammable refrigerant can possibly be released to the surrounding 
space. Prior to work taking place, the area around the equipment is to be surveyed 
to make sure that there are no flammable hazards or ignition risks. No Smoking 
signs shall be displayed.
•  Ventilated area
   Ensure that the area is in the open or that it is adequately ventilated before 
breaking into the system or conducting any hot work. A degree of ventilation shall 
continue during the period that the work is carried out. The ventilation should 
safely disperse any released refrigerant and preferably expel it externally into the 
atmosphere.