•  Checks to the refrigeration equipment
   Where electrical components are being changed, they shall be fit for the purpose 
and to the correct specification. At all times the manufacturer’s maintenance and 
service guidelines shall be followed. If in doubt consult the manufacturer’s technical 
department for assistance. The following checks shall be applied to installations 
using flammable refrigerants:
   The charge size is in accordance with the room size within which the refrigerant 
containing parts are installed;
   The ventilation machinery and outlets are operating adequately and are not 
obstructed;
   If an indirect refrigerating circuit is being used, the secondary circuit shall be 
checked for the presence of refrigerant; Marking to the equipment continues to 
be visible and legible. Markings and signs that are illegible shall be corrected; 
Refrigeration pipe or components are installed in a position where they are 
unlikely to be exposed to any substance which may corrode refrigerant containing 
components, unless the components are constructed of materials which are 
inherently resistant to being corroded or are suitably protected against being so 
corroded.
•  Checks to electrical devices
   Repair and maintenance to electrical components shall include initial safety checks 
and component inspection procedures. If a fault exists that could compromise 
safety, then no electrical supply shall be connected to the circuit until it is 
satisfactorily dealt with. If the fault cannot be corrected immediately but it is 
necessary to continue operation, an adequate temporary solution shall be used. 
This shall be reported to the owner of the equipment so all parties are advised.
   Initial safety checks shall include:
   That capacitors are discharged: this shall be done in a safe manner to avoid 
possibility of sparking; That there no live electrical components and wiring are 
exposed while charging, recovering or purging the system; That there is continuity 
of earth bonding.
•  Repairs to sealed components
   During repairs to sealed components, all electrical supplies shall be disconnected 
from the equipment being worked upon prior to any removal of sealed covers, 
etc. If it is absolutely necessary to have an electrical supply to equipment during 
servicing, then a permanently operating form of leak detection shall be located at 
the most critical point to warn of a potentially hazardous situation.
   Particular attention shall be paid to the following to ensure that by working on 
electrical components, the casing is not altered in such a way that the level of 
protection is aected. This shall include damage to cables, excessive number 
of connections, terminals not made to original specification, damage to seals, 
incorrect fitting of glands, etc.  Ensure that apparatus is mounted securely. Ensure 
that seals or sealing materials have not degraded such that they no longer serve 
the purpose of preventing the ingress of flammable atmospheres. Replacement 
parts shall be in accordance with the manufacturer’s specifications.
   NOTE: The use of silicon sealant may inhibit the eectiveness of some types of leak 
detection equipment. Intrinsically safe components do not have to be isolated prior 
to working on them.