•  Cabling 
Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, 
sharp edges or any other adverse environmental eects. The check shall also take into 
account the eects of aging or continual vibration from sources such as compressors or 
fans.
•  Detection of flammable refrigerants 
Under no circumstances shall potential sources of ignition be used in the searching for or 
detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) 
shall not be used.
•  Leak detection methods 
The following leak detection methods are deemed acceptable for systems containing 
flammable refrigerants. Electronic leak detectors shall be used to detect flammable 
refrigerants, but the sensitivity may not be adequate, or may need re-calibration. 
(Detection equipment shall be calibrated in a  refrigerant-free area.) Ensure that the 
detector is not a potential source of ignition and is suitable for the refrigerant used. Leak 
detection equipment shall be set at a percentage of the LFL of the refrigerant  and shall 
be calibrated to the refrigerant employed and the appropriate percentage of gas (25 % 
maximum) is confirmed. Leak detection fluids are suitable for use with most refrigerants 
but the use of detergents containing chlorine shall be avoided as the chlorine may react 
with the refrigerant and corrode the copper pipe-work. If a leak is suspected, all naked 
flames shall be removed/ extinguished. If a leakage of refrigerant is found which requires 
brazing, all of the refrigerant shall be recovered from the system, or isolated (by means 
of shut o valves) in a part of the system remote from the leak. Oxygen free nitrogen 
(OFN) shall then be purged through the system both before and during the brazing 
process.
•  Removal and evacuation 
When breaking into the refrigerant circuit to make repairs or for any other purpose 
conventional procedures shall be used. However, it is important that best practice is 
followed since flammability is a consideration. The following procedure shall be adhered 
to: Remove refrigerant; Purge the circuit with inert gas; Evacuate; Purge again with inert 
gas; Open the circuit by cutting or brazing. 
The refrigerant charge shall be recovered into the correct recovery cylinders. The system 
shall be flushed with OFN to render the unit safe. This process may need to be repeated 
several times. Compressed air or oxygen shall not be used for this task. Flushing shall be 
achieved by breaking the vacuum in the system with OFN and continuing to fill until the 
working pressure is achieved, then venting to atmosphere, and finally pulling down to a 
vacuum. This process shall be repeated until no refrigerant is within the system. When 
the final OFN charge is used, the system shall be vented down to atmospheric pressure 
to enable work to take place. This operation is absolutely vital if brazing operations on 
the pipe-work are to take place. Ensure that the outlet for the vacuum pump is not close 
to any ignition sources and there is ventilation available.
•  Charging procedures 
In addition to conventional charging procedures, the following requirements shall be 
followed. Ensure  that contamination of dierent refrigerants does not occur when using 
charging equipment. Hoses or lines shall be as short as possible to minimise the amount 
of refrigerant contained in them. 
Cylinders shall be kept upright. 
Ensure that the refrigeration system is earthed prior to charging the system with 
refrigerant. 
Label the system when charging is complete (if not already). 
Extreme care shall be taken not to overfill the refrigeration system. Prior to recharging 
the system it shall be pressure tested with OFN. The system shall be leak tested on 
completion of charging but prior to commissioning. A follow up leak test shall be carried 
out prior to leaving the site.