F20
DC over current fault of the
hardware
1. Check whether solar panel output current is within the
allowed range.
2. Check DC current sensor and its detection circuit.
3. Check if the inverter FW version is suitable for the hardware.
4. Restart the inverter, if the error still exists, please contact your
installer or Deye service.
F22
Contact your installer for help.
Crash stop (if there is a stop
button)
F21
Hardly appear the code. Never ever happened so far.
DC leakage flow fault
Error code Description Ongrid - Three Phase
F25 DC feedback fault Hardly appear the code. Never ever happened so far.
F27 DC end insulation error Hardly appear the code. Never ever happened so far.
F28 Inverter 1 DC high fault Hardly appear the code. Never ever happened so far.
F29 AC load switch failure Hardly appear the code. Never ever happened so far.
F32 Inverter 2 dc high fault Hardly appear the code. Never ever happened so far.
F33 AC over current Hardly appear the code. Never ever happened so far.
F34 AC current over load Hardly appear the code. Never ever happened so far.
F26
The DC busbar is unbalanced
1. Check whether the 'BUSN' cable or driver board power supply
cable is loose.
2. Restart the inverter, if the fault still exists, contact your
installer or Deye service.
F31
Relay open circuit fault
1. At least one Relay can't be closed. Check relays and its driver
signal. (Old inverter not have relays detection function)
2. Restart the inverter, if the fault still exists, contact your
installer or Deye service.
F35
No AC grid
1. Check AC grid voltage. Check AC voltage detection circuit.
Check if the AC connector in good condition. Check whether
the AC grid is normal in voltage.
2. Restart the inverter, if the fault still exists, contact your
installer or Deye service.
F30
AC main contactor failure
1. Check relays and AC voltage of relays.
2. Check relays driver circuit. Check if the software is not suitable
for this inverter. (Old inverter not have relays detection
function)
3. Restart the inverter, if the fault still exists, contact your
installer or Deye service.
F23
AC leakage current is transient
over current
1. This fault means the leakage current is above 30mA suddenly.
Check whether DC power supply or solar panels is ok, then
check 'Test data'-> 'diL'value is about 40; Then check the
leakage current sensor or circuit. Check test data needs
using big LCD.
2. Restart the inverter, if the fault still exists, contact your installer
or Deye service.
F24
DC insulation impedance failure
1. Check Vpe resistance on main board or detection on control board.
Check PV panels is OK. Many times this issue is the PV problem.
2. Check whether the PV panel (aluminum frame) is grounded well and
inverter is grounded well. Open the cover of inverter and then check
the inside ground cable is fixed well on the shell.
3. Check if the AC/DC cable, terminal block are shorted to ground or
the insulation is damaged.
4. Restart the inverter, if the fault still exists, contact your installer or
Deye service.