Deye SUN-60K-SG02HP3-EU-EM6 handleiding
Handleiding
Je bekijkt pagina 27 van 63

- 25 -
3.9 Data logger connection
For the configuration of data logger, please refer to the user manual of data logger. Wi-Fi logger is
not the only option, If the installation location does not have Wi-Fi signal or the signal is weak,
you can also choose a data logger that communicates via other interfaces.
The conductor should be made of the same metal as the phase conductors.
3.8 Earth Connection(mandatory)
Ground cable shall be connected to ground plate on grid side, this prevents electric shock if the
original protective conductor fails.
Earth Connection (Copper wires) (bypass)
Model
60/70/75/80kW
Wire Size
0AWG
Cross section(mm )
2
50
Torque value(max)
20.3Nm
Earth Connection (Copper wires)
Warning:
Inverter has built-in leakage current detection circuit,The type A RCD can be connected to
the inverter for protection according to the local laws and regulations.If an external leakage
current protection device is connected to the grid port of inverter, please refer to section
3.11, its operating current must be equal to 10mA/KVA or higher, for this series of inverter it
should be 800mA or higher, otherwise inverter may not work properly.
Model
60/70/75/80kW
Wire Size
0AWG
Cross section(mm )
50
Torque value(max)
20.3Nm
2