3.9 Data logger connection
For the configuration of data logger, please refer to the user manual of data logger. Wi-Fi plug is
not the only option, If the installation location does not have Wi-Fi signal or the signal is weak,
you can also choose a data logger that communicates via other interfaces.
The conductor should be made of the same metal as the phase conductors.
3.8 Earth Connection(mandatory)
Ground cable shall be connected to ground plate on grid side, this prevents electric shock if the
original protective conductor fails.
Earth Connection (Copper wires) (bypass)
Model
60/75/80kW
Wire Size
0AWG
Cross section(mm )
2
50
Torque value(max)
20.3Nm
Earth Connection (Copper wires)
Warning:
Inverter has built-in leakage current detection circuit,The type A RCD can be
connected to the inverter for protection according to the local laws and regula-
tions.If an external leakage current protection device is connected, its operating
current must be equal to 10mA/KVA or higher, for this series of inverter it should
be 800mA or higher, otherwise inverter may not work properly.
Model
60kW
75kW
Wire Size
0AWG
Cross section(mm )
50
Torque value(max)
20.3Nm
0AWG 50 20.3Nm
80kW 0AWG 50 20.3Nm
2