Deye SUN-45K-G04P3-EU-AM4-LV handleiding
Handleiding
Je bekijkt pagina 14 van 67

- 11 -
5.1 DC input terminal connection
5. Electrical Connection
1. Switch the Grid Supply Main Switch(AC)OFF.
2. Switch the DC lsolator OFF.
3. Assemble PV input connector to the inverter.
Warning:
When using PV modules, please ensure the PV+ & PV- of solar panel is not
connected to the system ground bar.
Warning:
Before connecting inverter, please make sure the PV array open circuit voltage is
within the 1000V of the inverter.
Safety Hint:
Before connection, please make sure the polarity of the output voltage of PV
array matches the “DC+” and “DC-” symbols.
Safety Hint:
Please use approved DC cable for PV system.
Table 5.1 DC Cable Specifications
Cable type
Range Recommended value
Cross section(mm )
Industry generic PV cable
(model: PV1-F)
2.5-4.0
(12-10AWG)
2.5(12AWG)
Pic 5.1 DC+ male connector
Pic 5.2 DC- female connector