Deye SUN-35K-G04P3-EU-AM4-LV handleiding

67 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 33 van 67
- 30 -
Note:
Select Meter option in Run Param and long press ENTER button to enter this
Meter Setting page.
Name Description
Exp_Mode
AVG: Average power of three phase is zero
exported.
MIN: Phase with minimum load power is zero
exported, while the other two phase may be
in purchase mode.
AVG/MIN
1-1000
1-1000
1-16
ON/OFF
1-999kW
OFF/Master/
Slave
ShuntQTY
Generator
G.CT
G.MFR
G.Pout
G.Cap
CT_Ratio
MFR
Shunt
CT ratio of power grid side meter when extern
CT is applied.
Manufacturer of the grid side meter. Modbus
Address of it should be set as 01.
Parallel mode. Set one inverter as Master,
others are Slave. ONLY need to set the master,
Slave will follow the settings in the master.
Number of inverters in parallel
DG side meter function Enable/Disable
CT ratio of power DG side meter when extern
CT is applied.
Manufacturer of the DG side meter. Modbus
Address of it should be set as 02.
Output power percentage of the DG.
Capacity of the DG.
Range
0-110%
0-110%
AUTO/CHNT/
EASTRON
AUTO/CHNT/
EASTRON
Feedin
Percentage of the Feed in power exported
to the grid.

Bekijk gratis de handleiding van Deye SUN-35K-G04P3-EU-AM4-LV, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkDeye
ModelSUN-35K-G04P3-EU-AM4-LV
CategorieNiet gecategoriseerd
TaalNederlands
Grootte6779 MB