Good grounded is important for resist the surge voltage shock and improve EMI's performance.
So before the connection of AC, DC, communication connections, inverter needs to ground first.
For a single system, just ground the PE cable; For multiple machine systems, all PE cables of the
inverter need to be connected to the same grounding copper platoon to ensure the equipotent
connection. The installation of the shell ground wire is shown as Pic 5.12. The external protective
earthing conductor is made of the same metal as the phase conductor.
5.3 Connection of the ground line
- 17 -- 16 -
Pic 5.12 The installation of the shell ground wire
RS4 85
lim iter1 limi ter2
Met er
WIF I
RS4 85
lim iter1 limi ter2
Met er
WIF I
Table 5.3 Recommened cable specifications
Warning:
Inverter has built-in leakage current detection circuit, The type A RCD can be
connected to the inverter for protection according to the local laws and regulations.
If an external leakage current protection device is connected, its operating current
must be equal to 300 mA or higher, otherwise inverter may not work properly.
Model
Wire Size
Torque value(max)
Cable(mm²)
SUN-35/40/45K-G-LV 12.4Nm
4AWG
16mm
SUN-50K-G-LV 16.9Nm
2AWG
25mm