- 24 -
3.8 Earth Connec�on(mandatory)
Ground cable shall be connected to ground plate on grid side this prevents electric shock. if the
original protec�ve conductor fails.
Note:
Iinverter has built–in leakage current detec�on circuit,If an external RCD is required,
a type-A RCD with rated residual current of 300mA or higher is suggested.Otherwise
inverter may not work properly
SUN-(3-5)K-SG04LP1-AU
SUN-6K-SG04LP1-AU
Model Wire Size Cable(mm )
2
Torque value(max)
3kW 10AWG 4.0 1.2Nm
3.6/5/6kW 8AWG 6.0 1.2Nm
Model Wire Size Cable(mm )
2
Torque value(max)
3/3.6/5/6kW 8AWG 6.0 1.2Nm
Earth connec�on (Copper wires) (Bypass)
Earth connec�on (Copper wires)