Meter SN:2
Power: 0W
󾙙󾙕

󾙔

Ensuring grid input cables connect 1&3 port of energy meter, and inverter AC output cables
connect 2&4 port of energy meter when connecting.

In final installation, breaker certified according to AS60947.3 shall be installed with the
equipment.
󾙙󾙔





󾙗
󾙖󾙚󾙗
󾙖󾙚󾙗
󾙖󾙚󾙗
󾙖󾙚󾙗


󾙖󾙚󾙗

󾙓
󾙔
󾙕
󾙖
󾙖󾙚󾙗

󾙓
󾙔󾙕󾙒󾙔
󾙗󾙘󾙙󾙚󾙛󾙓󾙒
󾙔
󾙕
 
󾙓 󾙔


󾙖
Warning:
Iinverter has built–in leakage current detec�on circuit,If an external RCD is
required,a type-A RCD with rated residual current of 300mA or higher is
suggested.Otherwise inverter may not work properly.