Deye SUN-29.9K-SG01HP3-EU-BM3 handleiding
Handleiding
Je bekijkt pagina 22 van 61

- 20 -
1 2 3 4 5 6 7 8 9 10 1112
White wire
Black wire
CT
Arrow�pointing
to�inverter
*Note:When taking power from the utility grid, if the grid power displayed
on the LCD screen is indeed negative, please adjust the installation direction
of the CTs.
Grid
N
PE
L1
L2
L3
CT1
CT2
CT3
Inverter
GRID
N
L1
L2
L3
3.7 Meter or CT installation
3.7.1 CT connection
There are three selectable installation methods to measure the power consumption or to ensure zero power
export to grid. The default installation method is to use the CTs(300A/5A) that come with the packaging
box. When the distance between the AC distribution box and the hybrid inverter exceeds 10 meters, which
means that the wire length of the CT needs to exceed 10 meters, it is recommended to use a smart meter
instead of three CTs. In addition, in a parallel system, if the current to be measured is greater than 300 A, the
default three CTs also need to be replaced with smart meters or larger CTs. Please contact the Deye support
team to confirm which specification of CT or smart meter to use.