Name Description
Exp_Mode
AVG: Average power of three phase is zero exported.
MIN: Phase with minimum load power is zero
exported, while the other two phase may be
in purchase mode.
AVG/MIN
1-1000
1-1000
1-16
ON/OFF
OFF/Master/
Slave
ShuntQTY
Generator
G.CT
G.MFR
CT_Ratio
MFR
Shunt
CT ratio of power grid side meter when extern CT is
applied.
Manufacturer of the grid side meter. Modbus
Address of it should be set as 01.
Parallel mode. Set one inverter as Master, others
are Slave. ONLY need to set the master, Slave will
follow the settings in the master.
Number of inverters in parallel
DG side meter function Enable/Disable
CT ratio of power DG side meter when extern CT is
applied.
Manufacturer of the DG side meter. Modbus
Address of it should be set as 02.
1-999kWG.Cap
Capacity of the DG.
Range
0-110%
AUTO/CHNT/
EASTRON
AUTO/CHNT/
EASTRON
Feedin
Percentage of the Feed in power exported to the
grid.
Note
: Select Meter option in Run Param and long press ENTER button to enter this
Meter Setting page.