Good grounding is good for resisting surge voltage shock and improving EMI performance.There-
fore, before connecting AC, DC and communication cables, you need to ground the cable firstly.
For a single system, just ground the PE cable. For multiple machine systems, all PE cables of the
inverter need to be connected to the same grounding copper platoon to ensure the equipoten-
tial connection. The installation of the shell ground wire is shown as picture 5.11. The external
protective earthing conductor is made of the same metal as the phase conductor.
Pic 5.11The installation of the shell ground wire
- 15 -
Warning:
Inverter has built-in leakage current detection circuit, The type A RCD can be
connected to the inverter for protection according to the local laws and regulations.
If an external leakage current protection device is connected, its operating current
must be equal to 300 mA or higher, otherwise inverter may not work properly.





SUN-18/20/21K-G04-LV 12.4Nm
6AWG 10mm² 10mm²