- 20 -
3.8 Earth Connec�on(mandatory)
Ground cable shall be connected to ground plate on grid side, this prevents electric shock if the
original protec�ve conductor fails.
Earth connec�on (Copper wires)
Warning:
Inverter has built-in leakage current detec�on circuit, The type A RCD can be
connected to the inverter for protec�on according to the local laws and regula�ons.
If an external leakage current protec�on device is connected, its opera�ng current
must be equal to 300 mA or higher, otherwise inverter may not work properly.
Model
5/6kW
Wire Size
8AWG
Cable(mm )
2
6.0
Torque value(max)
1.2Nm
7.6/8/10/12kW 6AWG 10 1.2Nm
Model
5/6kW
Wire Size
8AWG
Cable(mm )
2
6.0
Torque value(max)
1.2Nm
7.6/8/10/12kW 6AWG 10 1.2Nm
Earth connec�on (Copper wires) (bypass)