INSTALLATION & SERVICE MANUAL FOR PROFESSIONALS
Maintenance and care: Error list
A B C
Error
code
Error Possible cause
Action
required
Reset
16 R 2 E16 Firmware 2.9 and
up:
FPC fault (option)
Only active if the
"Fire Protection
Controller" acces-
sory is connected
to the unit.
No communica-
tion with the
re protection
controller
Fire protection
controller with
this address has
previously been
installed but can
no longer be
reached
Check connection
to re protection
controller
Perform a
manual reset
by pressing the
alarm button on
the control panel
or by turning the
unit o/on
There is no posi-
tion feedback for
re dampers
A re damper
is closed, but
should be open
Check power supply
to re dampers
Check re dampers
internal re detector
Error in monthly,
weekly or manual
test of re damp-
ers
Fire damper stuck
in either open or
closed position
The re damper is
blocked.
Fire dampers are con-
nected incorrectly
Fire damper defec-
tive