48
INSTALLATION & SERVICE MANUAL FOR PROFESSIONALS
Maintenance and care: Error list
A B C
Error
code
Error Possible cause
Action
required
Reset
13 - 0 E 13 Communication
error / poor signal
Shown only on
wireless remote
control
Try again every
5 minutes or
if a button is
pressed
No wireless signal The ventilation
unit is switched
o
Turn on the ventila-
tion system
Wireless signal is
too weak
Antenna not
mounted on unit
Install antenna
The remote con-
trol is too far from
the ventilation
system
Move it closer to the
ventilation system
Install antenna exten-
sion cable
14 R 2 E 14 Fire alarm
Duct-connected
re thermostat
(accessory)
Input is normally
closed (NC) but is
now open
Fire or smoke
sensor connected
to this input is
active
Check for smoke or
re
The alarm dis-
play can be reset
by pressing the
alarm button or
by turning the
unit o/on.
However, the
unit cannot be
started until the
alarm conditions
have disap-
peared
Check if sensor and
connection are OK
Nothing connect-
ed to this input
Install short circuit
accessory
15 R 1 E 15 High water level
sensor (accessory)
Water level too
high
Water outlet is
clogged
Clean the water
outlet
Automatic reset
when input is
closed again
The water outlet
is installed incor-
rectly
Check that the water
outlet is mounted on
the correct side and
that the pipes are not
above the drain level.
Auxiliary drain
pump not run-
ning.
Check the pump
Inspect fuse
The water level is
not too high
Water level sensor
disconnected
Check wiring
Water level sensor
normally open
(NO)
Congure or replace
the water level sen-
sor so it is normally
closed (NC).
Digital input
congured incor-
rectly
Check the congura-
tion of the digital
input using PC Tool