Dantherm HCV 700 handleiding
Handleiding
Je bekijkt pagina 46 van 60

46
INSTALLATION & SERVICE MANUAL FOR PROFESSIONALS
Maintenance and care: Error list
A
B C
Error
code
Error Possible cause
Action
required
Reset
4 R 1 E 4 Extract air tem-
perature sensor
(T1)
The control panel
measures that the
temperature sen-
sor is either open
or short-circuited
Temperature
sensors are not
mounted cor-
rectly
Mount temperature
sensors correctly
Automatic reset
if temperature
is within normal
range for 30
seconds
Resistance in one
of the tempera-
ture sensors is too
low or too high
Replace temperature
sensors
Temperature
sensor resistance
is OK
Replace control panel
5 R 1 E 5 Supply air tem-
perature sensor
(T2)
The control panel
measures that the
temperature sen-
sor is either open
or short-circuited
Temperature
sensors are not
mounted cor-
rectly
Mount temperature
sensors correctly
Automatic reset
if temperature
is within normal
range for 30
seconds
Resistance in one
of the tempera-
ture sensors is too
low or too high
Replace temperature
sensors
Temperature
sensor resistance
is OK
Replace control panel
6 R 1 E 6 Extract air tem-
perature sensor
(T3)
The control panel
measures that the
temperature sen-
sor is either open
or short-circuited
Temperature
sensors are not
mounted cor-
rectly
Mount temperature
sensors correctly
Automatic reset
if temperature
is within normal
range for 30
seconds
Resistance in one
of the tempera-
ture sensors is too
low or too high
Replace temperature
sensors
Temperature
sensor resistance
is OK
Replace control panel
7 R 1 E 7 Exhaust air tem-
perature sensor
(T4)
The control panel
measures that the
temperature sen-
sor is either open
or short-circuited
Temperature
sensors are not
mounted cor-
rectly
Fit temperature sen-
sors correctly
Automatic reset
if temperature
is within normal
range for 30
seconds
Resistance in one
of the tempera-
ture sensors is too
low or too high.
Replace temperature
sensors
Resistance in tem-
perature sensors
is OK
Replace control panel
8 - 0 E 8 Room air tem-
perature sensor
(T5)
Shown only on wireless remote control Automatic reset
9 - - E 9 Not used
10 R 0 E 10 Outdoor air tem-
perature < -13°C
- - Automatic re-
start after 1800
seconds
Bekijk gratis de handleiding van Dantherm HCV 700, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
Merk | Dantherm |
Model | HCV 700 |
Categorie | Niet gecategoriseerd |
Taal | Nederlands |
Grootte | 4620 MB |