Dantherm ACT-7 handleiding

92 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 4 van 92
4
Product description: Overall description
1
2
7
7
1
3
6
5
6
2
4
Front Rear
Fig. 3
Pos. Description Pos. Description
1 Support chain 5 Drain pipe
2 Carrying handle 6 Water pipe coupling (IN)
3 Electrical connection 7 Fan
4 Water pipe coupling (OUT) 8 Spacer
Specication Unit ACT 7 EU ACT 7 UK
Cooling capacity (max)
1
kW 7,0 7,0
Power Supply V/Hz 230/1ph/50
Power plug CEE 7/7 UK mains
Fuse A 16 13
Nominal current A 11,2 11
Power consumption (nominal) kW 2,6 2,5
Airow internal (stepless variable) m
3
/h 930-1310
Sound level (3 metres indoor - max. speed) dBA 56
Operating range - room temperature °C 8-35
Operating range - outdoor °C 0-40 0-35
Refrigerant / charge gram R407C/ 880
GWP (Global Warming Potential) 1774
CO
2
equivalent ton 1,561
Max length/height between in- and outdoor unit m 30/ 10
Surface powder coated RAL7047 Gloss 85 smooth
Outdoor unit
Sound level (3 metres - max speed) dbA 55 52
Weight kg 18,5 18
1: Outside conditions 28°C/60%RH
Illustration
(Heat exchanger)
Data sheet