Example 1
A1
dUdt
A
B
1
2
2
1
3
4
U
V
W
PE
5
5
e30bj127.10
Illustration 11: Example Installation 1
1
NFE units
2
AC chokes
3
FI13 (inverter unit)
4
dU/dt filter
5
DC busbars
Table 11: Cabinet Data for Installation Example 1
This installation applies to drive types:
NXP1150 5
NXP0920 6
NXP1030 6
NXP1180 6
Minimum required cabinet width:
600 mm (Cabinet A) + 800 mm (Cabinet B)
(23.62 in (Cabinet A) + 31.50 in (Cabinet B))
Minimum required cabinet height:
2200 mm
(86.61 in)
Required weight carrying capacity:
NXP1150 5: 480 kg (1058.2 lb) (Cab. A); 540 kg (1190.5 lb) (Cab. B)
NXP0920 6: 450 kg (992.1 lb) (Cab. A); 540 kg (1190.5 lb) (Cab. B)
NXP1030 6: 450 kg (992.1 lb) (Cab. A); 540 kg (1190.5 lb) (Cab. B)
NXP1180 6: 480 kg (1058.2 lb) (Cab. A); 540 kg (1190.5 lb) (Cab. B)
Protection rating:
This manual applies to IP21.
Construction:
According to EN60439-1
Ventilation openings:
See 5.2.1 Ventilation of the Cabinet.