Table 5: Available EMC Classes
EMC class in
IEC/EN
61800-3 + A1
VACON
®
equiva-
lent EMC
class
Description
Availa-
ble for
C4
T
These AC drives comply with the standard IEC/EN 61800-3 + A1 if they are used in IT
systems. In IT systems, the networks are isolated from ground, or connected to ground
through high impedance to decrease the leakage current.
N O T I C E
If the AC drives are used with other supplies, they do not comply with the EMC re-
quirements.
All prod-
ucts
No EMC emis-
sion protec-
tion
N
The AC drives of this category do not give EMC emission protection. These drives are
installed in enclosures.
N O T I C E
An external EMC filter is usually necessary to comply with the EMC emission require-
ments.
N O T I C E
RADIO INTERFERENCE
In a residential environment, this product can cause radio interference.
Take supplementary mitigation measures.
IP00
3.6 Control Panel
3.6.1 Keypad
The VACON
®
keypad has 9 buttons with which to control the AC drive (and motor), set parameters, and monitor values.
e30bf978.10
K
A B C
L
D
E
J
F
I H G
reset
ready
run
fault
select enter
Illustration 2: Keypad Buttons for VACON
®
NXP
AQ468246143802en-000201 / DPD00888 | 21Danfoss A/S © 2023.09
Product Overview
VACON® NXP IP00 Drive Modules
Operating Guide

Bekijk gratis de handleiding van Danfoss VACON NXP, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkDanfoss
ModelVACON NXP
CategorieNiet gecategoriseerd
TaalNederlands
Grootte20640 MB