Danfoss iC2-Micro handleiding

12 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 11 van 12
11Danfoss Drives · AD423936930805en-000501
Terminals
Attribute iC2-Micro VLT® Micro Drive FC 51
Terminal type Spring type Screw type
I/O terminals
Terminal number Type Terminal number Type
T12 24V T12 24V
T13 DI1 T18 DI1
T14 DI2 T19 DI2
T15 DIO T20 GND
T17 DI3 T27 DI3
T18 DI4 T29 DI4
T20 GND T33 DI5
T31 AO1 T42 AO1
T32 10V T50 10V
T33 AI1 T53 AI1
T34 AI2 T55 GND
T35 GND T60 AI2
01, 02, 03 Relay 01, 02, 03 Relay
Digital output
Programmable T15 could be set as digtal output.
Max. output current is 40 mA
Programmable T42 could be set as digtal output.
Max. output current is 20 mA
Pulse input Programmable T18 can be set as pulse input (4-32 kHz) Programmable T33 can be set as pulse input (20-5000 Hz)
Pulse output Programmable T15 can be set as pulse output (4-32 kHz) N.A.
Analog inputs mode
switch
By software paramter By hardware switch
PNP & NPN switch By software paramter By hardware switch
Illustration
Comparison of terminals
+24 V OUT
+10 V OUT
DI1
DI2
DIO
DI3
DI4
AO1
AI1
AI2
GND
GND
12 13 14 15 17 18 20 31 32 33 34 35
+ 24 V OUT
12
D IN
18
D IN
19
GND
20
D IN
27
D IN
29
D IN
33
A OUT
42
+ 10 V OUT
50
0 – 10 V A IN
53
GND
55
A IN
60
How to order
To order, go to store.danfoss.com and choose country/region.

Bekijk gratis de handleiding van Danfoss iC2-Micro, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkDanfoss
ModeliC2-Micro
CategorieNiet gecategoriseerd
TaalNederlands
Grootte15646 MB