Air Conditioner Service Manual
22
5.2.2 Installation Safety
1) Refrigerant Leak Detector
2) Appropriate Installation Location
The left picture is the schematic diagram of a refrigerant leak detector.
Please note that:
1. The installation site should be well-ventilated.
2. The sites for installing and maintaining an air conditioner using Refrigerant R454B should be free from open
fire or welding, smoking, drying oven or any other heat source higher than 396 which easily produces open fire.
3. When installing an air conditioner, it is necessary to take appropriate anti-static measures such as wear
anti-static clothing and/or gloves.
4. It is necessary to choose the site convenient for installation or maintenance wherein the air inlets and outlets
of the indoor and outdoor units should be not surrounded by obstacles or close to any heat source or
combustible and/or explosive environment.
5. If the indoor unit suffers refrigerant leak during the installation, it is necessary to immediately turn off the
valve of the outdoor unit and all the personnel should go out till the refrigerant leaks completely for 15 minutes.
If the product is damaged, it is a must to carry such damaged product back to the maintenance station and it is
prohibited to weld the refrigerant pipe or conduct other operations on the user's site.
6. It is necessary to choose the place where the inlet and outlet air of the indoor unit is even.
7. It is necessary to avoid the places where there are other electrical products, power switch plugs and sockets,
kitchen cabinet, bed, sofa and other valuables right under the lines on two sides of the indoor unit.