Water Discharge Test
• Before the test, make sure that the water discharge pipeline is smooth, and
check that each connection is sealed properly.
• Conduct the water discharge test in the new room before the ceiling is paved.
1. Connect the power supply, and set the air conditioner to operate in the cool
mode. Check the running sound of the drainage pump.
2. Keep cool mode running at least 10 min.
3. Stop the air conditioner. Wait for three minutes, and then check if there is
anything unusual. If the water discharge iping layout is not correct, the exces-
sive water flow will cause the water level error and “EE” error code will be
displayed on the display panel. There may even be water overflowing from
the water pan.
4. Continue to add water until the alarm for excessive water levels is triggered.
Check if the drainage pump drains water immediately. After three minutes, if
the water level does not fall below the warning level, the unit will shut down.
At this time, you need to turn o the power supply, and drain away the accu-
mulated water before you can turn on the unit normally.
5. Turn o the power supply, remove the water manually using the drainage
plug, and put the test cap back to the original place.
The drainage plug at the bottom of the unit body is used to discharge accumu-
lated water from the drain pan when the air conditioner malfunctions. When the
air conditioner is operating normally, make sure the drainage plug is properly
plugged to prevent water from leaking.