16
4.2 Commissioning
4.2.1 Set Master Indoor Unit
Under Off status, long press “MODE” button for 5s to set the
corresponding indoor unit of wired controller as master indoor unit. If
the system mode priority is the master-slave mode, “
” icon will be
light after nishing setting.
NOTES:
There is a master indoor unit in a system, other slave indoor
units can be set as master unit, in which case, the original
master unit will become a slave unit.
This function is not applicable to partial units.
4.2.2 Parameter Enquiry
Unit parameters can be checked in unit On or Off status.
(1) Long press “FUNCTION” button for 5s to enter the inter-
face of viewing unit parameters. “C00” is displayed in tem-
perature zone.
(2) Press “+” or “-” button to select parameter code.
(3) Press “ENTER” button to return to last step until exits
viewing parameters.
The parameter enquiry list is as following: