Daikin VKM50GBV1 handleiding
Handleiding
Je bekijkt pagina 17 van 20

3P130767-4K English 13
Shortening of “maintenance cycle” and “replacement
cycle” needs to be considered in the following cases.
• When used in hot, humid locations or locations where tem-
perature and humidity fluctuate greatly.
• When used in locations where power fluctuation (voltage, fre-
quency, wave distortion, etc.) is high.
(Cannot be used if it is outside the allowable range.)
• When installed and used in locations where bumps and
vibrations are frequent.
• When used in bad locations where dust, salt, harmful gas or
oil mist such as sulfurous acid and hydrogen sulfide may be
present in the air.
• When used in locations where the machine is started and
stopped frequently or operation time is long. (Example:
24 hour air-conditioning)
• When the supply water is hard water the humidifier’s life
become shorter.
RECOMMENDED REPLACEMENT CYCLE OF WEAR-
OUT PARTS
[The cycle is not the same as the warranty period.]
• Table 2 “Replacement Cycle” Lists
Note 1
This table indicates main parts.
See the maintenance and inspection contract for details.
Note 2
This maintenance cycle indicates recommended lengths of
time until the need arises for maintenance work, in order to
ensure the product is operational as long as possible.
Use for appropriate maintenance design (budgeting mainte-
nance and inspection fees, etc.).
Note 3
Life of humidifying element is about 3 years (4,000 hours),
under the supply water conditions of hardness: 150mg/l.
(Life of humidifying element is about 1 year (1,500 hours),
under the supply water conditions of hardness: 400mg/l.)
Annual operating hours: 10 hours/day × 26 days/
month × 5 month = 1,300 hours.
Contact your local dealer for details.
Note: Breakage due to taking apart or cleaning inside by any-
one other than our authorized dealers may not be included in
the warranty.
MOVING AND DISCARDING THE UNIT
• Contact your local dealer for removing and reinstalling the
total enthalpy heat exchanger when moving house since
they require technical expertise.
• This unit contains chlorofluorocarbon in the refrigerant.
When discarding, removing installing and maintaining the
unit, collect the refrigerant in accordance with the local law
for the global environmental destruction prevention.
In detail contact your local dealer.
WHERE TO CALL
For after-sales service, etc., consult with your local dealer.
WARRANTY PERIOD
Warranty period: Within one year after
installation.
• If it is necessary to repair the air conditioner within the war-
ranty period, contact your local dealer.
Name of Main Part
Inspection
Cycle
Replacement Cycle
Air filter
1 year
3 years
High efficiency filter
(Optional accessory)
1 year
Heat exchanger element
2 years 10 years
Humidifier element 1 year 3 years (Note 3)