13Configuration
Installation and operation manual
20
VAM350~2000J8VEB
Heat reclaim ventilation unit
4P664011-1 – 2021.08
13.2 Field settings
Refer to the installer and user reference guide of the user interface for more information on how to change field settings.
Mode SW SW description SW position
(a)
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15
17(27) 0 Filter cleaning time ±2500 hours ±1250 hours
1 Nighttime free cooling timer (after stop)
(b)
OFF ON after 2hours ON after 4hours ON after 6hours ON after 8hours
2 Precool/preheat
(c)
OFF ON
3 Precool/preheat duration
(c)
30 minutes 45 minutes 60 minutes
4 Initial fan speed
(d)
High Ultra-high
5
(e)
Yes/No setting for duct connection with VRV
system
Without duct With duct Without duct With duct Without duct With duct
Setting for cold areas (fan operation when
heater thermostat is OFF)
(f)
Stop/Stop Low/Low Stop/stop Low/Low
Fan operation during defrost/oil return/hot
start
(f)
Stop/Stop Stop/Stop Stop/Stop Stop/Stop Stop/— Stop/Stop Stop/—
17(27) 6 Nighttime free cooling (fan settings)
(b)
High Ultra-high
7 Target temperature for independent nighttime
free cooling
(b)
18°C 19°C 20°C 21°C 22°C 23°C 24°C 25°C 26°C 27°C 28°C 29°C 30°C
8 Central zone link No Yes
9 Preheat time extension
(c)
0
minutes
30
minutes
60
minutes
90
minutes
18(28) 0 External signal
(g)
JC/J2 Last command Priority on
external input
Priority on
operation
Disable nighttime
free cooling/
Perform forced
stop
24 hours
ventilation ON/
OFF
Disable JC/J2
1 Direct power ON OFF ON
2 Auto restart
(h)
OFF ON
3 Output signal to external damper (X24A) Damper output
(fan operation)
Damper output
(fan operation)
4 Indication of ventilation mode ON OFF
18(28) 6 Automatic ventilation air flow mode Linear Fixed A Fixed B
7 Fresh-up mode Supply – no
indication
Exhaust – no
indication
Supply –
indication
Exhaust –
indication
8 External input terminal function selection
(i)
(JC/
J1)
Fresh-up Error output Error output and
stop operation
Forced off Fan forced off Air-flow up
9 BRP4A50A output switching selection
(between X3 and X4)
Heater output Error output Fan output (Low/
High/Ultra-high)
Fan output (High/
Ultra-high)
Fan output (Ultra-
high)
Fan output (Low/High/Ultra-high)
(between X1 and X2) Operation output Operation output
10 EKVDX connected?
(j)
No Yes
18(28) 11 Filter contamination check No action Reset filter check Force filter check
13 Cooling set point (with EKVDX) 13°C 15°C 16°C 17°C 18°C 19°C 20°C 21°C 22°C 23°C 24°C 25°C 26°C 28°C 30°C
14 Heating set point (with EKVDX) 24°C 26°C 27°C 28°C 29°C 30°C 31°C 32°C 33°C 35°C 37°C 39°C 41°C 43°C 45°C