(Annex DD.4.3) Work procedure
Work shall be undertaken under a controlled procedure so as to minimise the risk of a ammable gas or vapour being
present while the work is being performed.
(Annex DD.4.4) General work area
All maintenance sta and others working in the local area shall be instructed on the nature of the work being carried
out. Work in conned spaces shall be avoided.
(Annex DD.4.5) Checking for presence of refrigerant
The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician
is aware of potentially toxic and ammable atmospheres.
Ensure that the refrigerant or leak detection equipment being used is suitable for use with the refrigerant applicable
to the unit, i.e. non-sparking, adequately sealed or intrinsically safe.
(Annex DD.4.6) Presence of re extinguisher
If any hot work is to be conducted on the unit requiring an increase in the temperature of parts of the unit (e.g. brazing),
appropriate re extinguishing equipment shall be available to hand. Have a dry powder or CO2 re extinguisher
adjacent to the refrigerant charging area.
(Annex DD.4.7) No ignition sources
No person carrying out work in relation to a unit shall use any sources of ignition in such a manner that it may lead to
the risk of re or explosion. All possible ignition sources, including cigarette smoking, should be kept suciently far
away from the site of installation, repairing, removing and disposal of the unit, during which ammable refrigerant can
possibly be released to the surrounding space. Prior to work taking place, the area around the unit is to be surveyed
to make sure that there are no ammable hazards or ignition risks. “No Smoking” signs shall be displayed.